orgasesinyourenvironmenthavecauseddamagetotheserver,Lenovomayconditionprovisionofrepair
orreplacementofserversorpartsonimplementationofappropriateremedialmeasurestomitigatesuch
environmentalcontamination.Implementationofsuchremedialmeasuresisacustomerresponsibility.
Table28.Limitsforparticulatesandgases
ContaminantLimits
Particulate
•Theroomairmustbecontinuouslylteredwith40%atmosphericdustspotefciency
(MERV9)accordingtoASHRAEStandard52.2
1
.
•Airthatentersadatacentermustbelteredto99.97%efciencyorgreater,using
high-efciencyparticulateair(HEPA)ltersthatmeetMIL-STD-282.
•Thedeliquescentrelativehumidityoftheparticulatecontaminationmustbemorethan60%
2
.
•Theroommustbefreeofconductivecontaminationsuchaszincwhiskers.
Gaseous•Copper:ClassG1asperANSI/ISA71.04-1985
3
•Silver:Corrosionrateoflessthan300Åin30days
1
ASHRAE52.2-2008-MethodofTestingGeneralVentilationAir-CleaningDevicesforRemovalEfciencybyParticle
Size.Atlanta:AmericanSocietyofHeating,RefrigeratingandAir-ConditioningEngineers,Inc.
2
Thedeliquescentrelativehumidityofparticulatecontaminationistherelativehumidityatwhichthedustabsorbs
enoughwatertobecomewetandpromoteionicconduction.
3
ANSI/ISA-71.04-1985.Environmentalconditionsforprocessmeasurementandcontrolsystems:Airborne
contaminants.InstrumentSocietyofAmerica,ResearchTrianglePark,NorthCarolina,U.S.A.
PolyvinylChloride(PVC)cableandcordnotice
WARNING:Handlingthecordonthisproductorcordsassociatedwithaccessoriessoldwiththisproduct
willexposeyoutolead,achemicalknowntotheStateofCaliforniatocausecancer,andbirthdefectsor
otherreproductiveharm.Washhandsafterhandling.
Recyclinginformation
Lenovoencouragesownersofinformationtechnology(IT)equipmenttoresponsiblyrecycletheirequipment
whenitisnolongerneeded.Lenovooffersavarietyofprogramsandservicestoassistequipmentownersin
recyclingtheirITproducts.ForinformationonrecyclingLenovoproducts,goto:
http://www.lenovo.com/lenovo/environment/recycling